Analog
Input
•Type : mV, V , mA
•Channels : 1
•Voltage range : ± 150mA, ± 500mV, ± 1V, ± 5V,
± 10V
•Current range : +/- 20mA
•Resolution : 12-bit
•Sampling rate : 100 Samples/Second
•Bandwidth
: 52.4 Hz
•Accuracy : ± 0.25% or better
•Zero drift : ± 20uV/°C
•Span
dri f: ± 25ppm/C
•CMR @ 50/60 Hz : 86 dB
•NMR @ 50/60 Hz : 100 dB
•Over voltage protection : 10V (P-P)
•Isolation
: 3000Vrms
Digital Input
•Channel
: 1
•Logic Level 0 : + 1V max
•Logic Level 1 : + 3.5V to 30V
Event Counter
•Max
Input Frequency : 50Hz
•Min. Pulse Width : 1 mS
|
Digital
Output
•Channels
: 2
•Open collector to 30V
•Output Load : sink 30mA max.
•Power dissipation : 300mW
Display LED
•4
1/2 digits
Communication Interface
•RS-485
Power Supply
•Input
: +10 to +30 Vdc
•Consumption
: 1.9W
|
|