Analog
Input
•Photo-isolation: 3750 Vrms
•Channel : 3
•Input Type : Pt , Ni
•Sampling rate: 15/12.5 samples/second
while filter at 60/50Hz
•Bandwidth: 15.7 Hz
•Wire connection : 2/3/4 wire
•Accuracy: ±0.1%
•Zero
Drift: ± 0.5uV/°C
•Span
drift: ± 25uV/°C
•CMR
@ 50/60 Hz: 150 dB min
•NMR
@ 50/60 Hz: 100 dB min
Communication Interface
•RS-485
Power
Supply
•Input
: +10 to +30 Vdc
•Consumption
: 1.0W
|
RTD
temperature range
Pt100 α=0.00385
Pt100 α=0.003916
Ni 120
Pt1000 α=0.00385
Pt100
|
-100 °C |
to |
+100°C |
a =0.00385 |
Pt100
|
0°C |
to |
+100°C |
a =0.00385 |
Pt100
|
0°C |
to |
+200°C |
a =0.00385 |
Pt100
|
0°C |
to |
+600°C |
a =0.00385 |
Pt100
|
-100 °C |
to |
+100°C |
a =0.003916 |
Pt100
|
0°C |
to |
+100°C |
a =0.003916 |
Pt100
|
0°C |
to |
+200°C |
a =0.003916 |
Pt100
|
0°C |
to |
+600°C |
a =0.003916 |
Ni120
|
-80°C |
to |
+100°C |
|
Ni120
|
0°C |
to |
+100°C |
|
|
|