Analog
Input
•Type : mV, V , mA (with external 125 ohms
resistor)
•Thermocouple : Type J, K, T, E, R, S, B,
N, C
•Channels : 1
•Voltage range : +/-15mV, +/-50mV, +/-100mV,
+/- 500mV , +/-1V,+/- 2.5V
•Current range : +/- 20mA
•Resolution : 16-bit
•Sampling rate : 10 Samples/Second
•Bandwidth
: 5.4 Hz
•Input impedance : 20M ohms
•Accuracy : ±0.05%
•Zero Drift : ± 0.5uV/°C
•Span
Drift : 25ppm/°C
•CMR @ 50/60 Hz : 150 dB
•NMR @ 50/60 Hz : 100 dB
•Over voltage protection : 10V (P-P)
•Isolation
: 3000Vrms
Digital Input
•Channel
: 1
•Logic Level 0 : + 1V max
•Logic Level 1 : + 3.5V to 30V
Event Counter
•Max Input Frequency : 50Hz
•Min.
Pulse Width : 1 mS
|
Digital
Output
•Channels
: 2
•Open
collector to 30V
•Output Load :
sink 30mA max.
•Power
dissipation : 300mW
Communication
Interface
•RS-485
Power Supply
•Input
: +10 to +30 Vdc
•Consumption
: 0.9W
Thermocouple type : (°C)
Type |
Range
(°C) |
J
|
-210 ~ +760 |
K
|
-270 ~ +1372 |
T |
-270 ~ +400 |
E |
-270 ~ +1000 |
R |
0 ~ +1768 |
S |
0 ~ +1768 |
B |
0 ~ +1820 |
N |
-270 ~ 1300 |
C |
0 ~ 2320 |
|

|